HV500 Technical Information

Application
InterruptedRating ( Ith )Uninterrupted
Thermal Current Rating 250A 500A
Intermittent Current Rating:
30% Duty 455A 915A
40% Duty 395A 790A
50% Duty 355A 705A
60% Duty 325A 645A
70% Duty 300A 600A
Rated Fault Current Breaking Capacity (Icn) 5ms Time Constant: (In accordance with UL583*)
Blowouts -
No Blowouts -
Rated Fault Current Breaking Capacity (Icn) Resistive Load: (In accordance with UL508*)
Blowouts -
No Blowouts 2000A at 500V D.C.
Maximum Recommended Contact Voltages
Blowouts - -
No Blowouts 500V 500V
Typical Voltage Drop per pole across New Contacts at 100A 30mV

Mechanical Durability > 1,000,000 Cycles
Coil Voltage Available (Us) (Rectifier board required for A.C.) 12 - 96V